TCX (I) 150/250V 19P0.75

Description

Description

Standards

  • Product
    IEC 60092-375
  • Installation
    IEC 60092-3
  • Test
    IEC 60332-3 Cat.A; IEC 60754-1; IEC 60754-2; IEC 61034
  • International
    IEC 60298

Application

TCX® (I) 150/250 V armoured individually screened twisted pair cables are used for telecommunication and instrumentation purposes. These cables provide strong protection aganist cross-talk in both low and high frequency runs, making them suitable for highly polluted electromagnetic surroundings. TCX®(I) cables are also selected where enhanced mechanical protection is required. Designed with halogen-free fire retardant materials, they provide optimum safety for people and maximal asset protection against all risks of fire.

 

Design

  1. Conductor:
    Stranded bare copper class 2
     
  2. Insulation:
    XLPE (cross-linked polyethylene)
     
  3. Individual screen:
    Alu/polyester tape with a tinned copper drain wire
     
  4. Assembling:
    Polyester tape
     
  5. Armour:
    Bare copper braid
     
  6. Outer sheath:
    Polyolefin SHF1 (SHF2 on request)
    Colour : grey 
     

Marking

NEXANS 279 TCX (I) Nber of pairs/triads & cross section 150/250V 90C IEC 60092-376 IEC 60332-3-22 Cat. A WW YYYY *CE* Manufacturing n° + metric marking

 

Core identification

Pair: white / blue with printed pair number
Triad: white / blue / red with printed triad number

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Halogen free
IEC 60754-1
Conductor material
Bare copper
Conductor flexibility
Stranded class 2
Insulation
XLPE (Cross-linked Polyethylene)
Individual screen
Tinned copper drain wire + aluminium/polyester tape
Inner covering
Polyester tape(s)
Armour type
Bare copper braid
Outer sheath
Polyolefin
Sheath colour
Grey
Drain wire
-
Number of conductors
-

Dimensional characteristics

Dimensional characteristics

Number of pairs
19
Number of triples
-
Conductor cross-section
0.75 mm²
Nominal outer diameter
22.8 mm
Minimum outer diameter
21.5 mm
Maximum outer diameter
24.5 mm
Approximate weight
768 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
150 / 250 (300) V
Max. DC resistance of the conductor at 20°C
52 Ohm/km

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Fire retardant
EN IEC 60332-3-22 (cat A)
Flame retardant
IEC 60332-1
Gases corrosivity
IEC 60754-2
Smoke density
IEC 61034
Electro magnetic interference resistance
Yes
Operating temperature, range
-30 ... 80 °C
Standard
IEC

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close